March 2011 |
UPS King Pro 1200 VA

GENERAL INFORMATION
|
 |
| Model Type |
KING PRO |
 |
| Model Name |
KIN-1200AP |
 |
 |
INPUT
|
 |
 |
DC INPUT
|
 |
 |
AC INPUT
|
 |
| AC Input Capacity on Battery |
1200VA |
 |
| AC Input Voltage |
(+/-) 25% at line input |
 |
| AC Input Frequency |
50 or 60 Hz+/-10% (auto sensing) |
 |
 |
OUTPUT
|
 |
 |
AC OUTPUT
|
 |
| AC Output Voltage |
Simulated sine ware at 100V or 110V/115V/120V or 220V/230V/240V +/-5% |
 |
| AC Output Frequency |
50 or 60 Hz +/- 0.5% |
 |
| AC Output Voltage Regulation |
AVR
automatically increase output voltage 15% above input voltage if -9% to
-25% of nominal. AVR decrease output voltage 13% below input voltage if
+9% to +25% of nominal |
 |
| AC Output Transfer |
2/4 milliseconds, including detection time |
 |
 |
AVR
|
 |
 |
EFFICIENCY
|
 |
 |
TRANSFER
|
 |
 |
NOISE
|
 |
 |
PROTECTION
|
 |
| Protection Spike |
320 Joules, 2ms |
 |
| Protection EMI/RFI |
10dB at 0.15 MHz, 50 dB at 30 MHz |
 |
| Protection Overload |
UPS automatic shutdown if overload exceeds 110% nominal at 60 sec and 130% at 3 sec |
 |
| Protection Unit |
Fuse for overload & short circuit protection |
 |
| Protection 10 BaseT |
Network (UTP, RJ-45) compatible jacks |
 |
| Protection Short Protection |
UPS output cut off immediately or input fuse protection |
 |
 |
BATTERY
|
 |
| Battery Type |
Sealed, Maintenance-free lead acid, with 3 - 6 years typical lifetime |
 |
| Battery Typical |
4 hours (to 90% of full capacity) |
 |
| Battery Protection |
Automatic self-test & discharge protection, replace battery indicator |
 |
| Battery Run Time |
65 - 75 minutes |
 |
 |
BACKUP TIME
|
 |
 |
PHYSICAL
|
 |
| Physical Weight kgs Tower |
15.2 |
 |
| Physical Weight lbs Tower |
(33.4lb) |
 |
| Physical Dimension mm Tower |
130x382x201 |
 |
| Physical Dimension inch Tower |
(5.1 |
 |
 |
INDICATOR
|
 |
| LCD |
LCD |
 |
| LED |
LED |
 |
 |
MAINTENANCE
|
 |
 |
ALARM
|
 |
| Alarm Battery Backup |
Slow beeping sound (about 0.47 Hz) |
 |
| Alarm Battery Low |
Rapid beeping sound (about 1.82Hz) |
 |
| Alarm Overload |
Continue beeping sound |
 |
 |
CONFORMANCE
|
 |
 |
INTERFACE
|
 |
| Interface RS-232 |
Bi-directional communication port |
 |
 |
ENVIRONMENT
|
 |
| Environment Ambient |
3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg c |
 |
| Environment Audible |
<40dBA (1 meter from surface) |
 |
| ShowOrder |
18 |
|
Click here to return
|