Menu Content/Inhalt
Home arrow Knowledge Base arrow Other Products arrow #7K22 - UPS KINGPRO 2200VA

#7K22 - UPS KINGPRO 2200VA Print
March 2011
#7K22 King Pro 2200 VA
kin2200fb.JPG
GENERAL INFORMATION
Model Type KING PRO
Model Name KIN-2200AP
AC INPUT
AC Input Capacity on Battery 2200VA
AC Input Voltage (+/-) 25% at line input
AC Input Frequency 50 or 60 Hz+/-10% (auto sensing)
AC OUTPUT
AC Output Voltage Simulated sine ware at 100V or 110V/115V/120V or 220V/230V/240V +/-5%
AC Output Frequency 50 or 60 Hz +/- 0.5%
AC Output Voltage Regulation AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal
AC Output Transfer 2/4 milliseconds, including detection time
PROTECTION
Protection Spike 320 Joules, 2ms
Protection EMI/RFI 10dB at 0.15 MHz, 50 dB at 30 MHz
Protection Overload UPS automatic shutdown if overload exceeds 110% nominal at 60 sec and 130% at 3 sec
Protection Unit Fuse for overload & short circuit protection
Protection 10 BaseT Network (UTP, RJ-45) compatible jacks
Protection Short Protection UPS output cut off immediately or input fuse protection
BATTERY
Battery Type Sealed, Maintenance-free lead acid, with 3 - 6 years typical lifetime
Battery Typical 4 hours (to 90% of full capacity)
Battery Protection Automatic self-test & discharge protection, replace battery indicator
Battery Run Time 85 - 95 minutes

Battery Backup Time

Battery Backup Time
Half Load                          7 Minutes
Battery Back Time                
Full Load                           15 Minutes

PHYSICAL
Physical Weight kgs Tower 30
Physical Weight lbs Tower (66lb)
Physical Dimension mm Tower 170x450x215
Physical Dimension inch Tower (6.7
INDICATOR
LED LED
ALARM
Alarm Battery Backup Slow beeping sound (about 0.47 Hz)
Alarm Battery Low Rapid beeping sound (about 1.82Hz)
Alarm Overload Continue beeping sound
INTERFACE
Interface RS-232 Bi-directional communication port
ENVIRONMENT
Environment Ambient 3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg c
Environment Audible <40dBA (1 meter from surface)
ShowOrder 20


Click here to return