March 2011 |

GENERAL INFORMATION
|
 |
| Model Type |
VANGUARD 2U |
 |
| Model Name |
VGD-1000 VA
|
 |
 |
AC INPUT
|
 |
| AC Input Capacity on Battery |
1000VA |
 |
| AC Input Voltage |
100V or 110V/120V/127V or 208V/220V/230V/240V |
 |
| AC Input Frequency |
50/60 Hz +/-0.5% |
 |
 |
AC OUTPUT
|
09
 |
| AC Output Waveform |
Sinewave |
 |
| AC Output Voltage |
100V or 110V/120V/127V or 208V/220V/230V/240V +/-2% |
 |
| AC Output Frequency |
50/60 Hz +/-0.5% |
 |
| AC Output Transfer |
0 ms |
 |
| AC Output Efficiency |
>95% |
 |
| AC Output Hamonic distortion |
<3% of T.H.D. at linear load |
 |
| AC Output Crest factor ratio |
3 : 1 |
 |
 |
PROTECTION
|
 |
| Protection Spike |
1015 Joules |
 |
| Protection Surge Protection |
120V (IEEE C62.41) / 230V (IEEE C61000-4-5 level 3) |
 |
| Protection Overload Protection |
125% for 1 minutes and 150% for 10 seconds |
 |
| Protection Short Circuit |
UPS output cut off immediately or input fuse/circuit breaker protection |
 |
 |
BATTERY
|
 |
| Battery Type |
sealed, maintenance-free lead acid batteries |
 |
| Battery Typical |
Recharge time to 90% full: 4 hours |
 |
| Battery Protection |
cut off without draining any current when battery is low |
 |
 |
BACKUP TIME
|
 |
| Battery Backup Time Full Load |
1u=4 min, 2u=7 min |
 |
| Battery Backup Time Half Load |
1u=10 min, 2u=15 min |
 |
 |
PHYSICAL
|
 |
| Physical Weight kgs RM |
1u=15.5, 2u=17.1 |
 |
| Physical Weight lbs RM |
1u=34.1, 2u=37.6 |
 |
| Physical Shipping Weight kgs |
1u=17.5, 2u=19.3 |
 |
| Physical Shipping Weight lbs |
1u=38.5, 2u=42.5 |
 |
| Physical Dimension mm RM |
1u=428x525x44, 2u=428x425x84 |
 |
| Physical Dimension inch RM |
1u=16.9x20.7x1.7, 2u=16.9x16.7x3.3 |
 |
| Physical Input Inlet |
NEMA 5-15 (120V) / IEC 320 (230V) |
 |
| Physical Receptacles |
NEMA 5-15 (120V) / IEC 320 (230V) |
 |
 |
INDICATOR
|
 |
| Indicator LCD |
Input/output voltage, frequency, on-line mode, back up mode, battery capacity, load level |
 |
 |
ALARM
|
 |
| Alarm Battery Backup |
Beep every 5 sec |
 |
| Alarm UPS Fault |
Continuous beeping sound and LCD display |
 |
 |
CONFORMANCE
|
 |
| Conformance Safety |
UL 1778, CE |
 |
 |
INTERFACE
|
 |
| Interface RS-232 |
Serial Port & USB |
 |
| Interface Option |
SNMP card |
 |
 |
ENVIRONMENT
|
 |
| Environment Temperature |
-20 ~ 50C / -4 ~ 122F |
 |
| Environment Humidity |
0 - 95%, non-condensing |
 |
| Environment Operation Temperature |
0 - 40C / 32 - 104F |
 |
| Environment Operation Elevation |
3500 meters max |
 |
| ShowOrder |
0 |
|
Click here to return
|