March 2011 |

GENERAL INFORMATION
|
 |
| Model Type |
VANGUARD RM |
 |
| Model Name |
VGD-6000RM |
 |
 |
AC INPUT
|
 |
| AC Input Capacity on Battery |
6000VA |
 |
| AC Input Voltage |
208V/220V/230V/240V |
 |
| AC Input Frequency |
50/60 Hz Auto Sensing |
 |
 |
AC OUTPUT
|
% 9  |
| AC Output Waveform |
Sine wave |
 |
| AC Output Voltage |
208V/220V/230V/240V +/-2% |
 |
| AC Output Frequency |
50Hz/60Hz +/-0.5% |
 |
| AC Output Transfer |
0 ms |
 |
| AC Output Efficiency |
>95% |
 |
| AC Output Hamonic distortion |
<3% of T.H.D. at linear load |
 |
| AC Output Crest factor ratio |
3:1 |
 |
 |
PROTECTION
|
 |
| Protection Surge Protection |
IEEEC61000-4-5 level 3 |
 |
| Protection Overload Protection |
125% for 1 minutes and 150% for 10 seconds |
 |
| Protection Short Circuit |
UPS output cut off immediately or input fuse/circuit breaker protection |
 |
 |
BATTERY
|
 |
| Battery Type |
sealed, maintenance-free lead acid batteries |
 |
| Battery Typical |
Recharge time to 90% full: 3 hours |
 |
| Battery Protection |
cut off without draining any current when battery is low |
 |
| Battery DC Voltage |
240V |
 |
 |
BACKUP TIME
|
 |
| Battery Backup Time Full Load |
7 min |
 |
| Battery Backup Time Half Load |
18 min |
 |
 |
PHYSICAL
|
 |
| Physical Weight kgs RM |
66 |
 |
| Physical Weight lbs RM |
145.2 |
 |
| Physical Shipping Weight kgs |
75.5 |
 |
| Physical Shipping Weight lbs |
166.1 |
 |
| Physical Dimension mm RM |
428x597x130 |
 |
| Physical Input Inlet |
hardwire |
 |
| Physical Receptacles |
hardwire |
 |
 |
INDICATOR
|
 |
| Indicator LCD |
Input/output voltage, frequency, on-line mode, backup mode, battery capacity, load level |
 |
 |
ALARM
|
 |
| Alarm Battery Backup |
Beep every 5 sec |
 |
| Alarm UPS Fault |
Continuous beeping sound and LCD display |
 |
 |
CONFORMANCE
|
 |
| Conformance Safety |
UL 1778, CE |
 |
 |
INTERFACE
|
 |
| Interface RS-232 |
Serial Port and USB |
 |
| Interface Option |
SNMP card |
 |
 |
ENVIRONMENT
|
 |
| Environment Temperature |
-20 ~ 50C / -4 ~ 122F |
 |
| Environment Humidity |
0 - 95%, non-condensing |
 |
| Environment Operation Temperature |
0 - 40C / 32 - 104F |
 |
| Environment Operation Elevation |
3500 meters max |
 |
| ShowOrder |
0 |
|
Click here to return
|