GENERAL INFORMATION
|
 |
| Model Type |
VANGUARD 2U |
 |
| Model Name |
VGD-1000 VA
|
 |
 |
AC INPUT
|
 |
| AC Input Capacity on Battery |
1000VA |
 |
| AC Input Voltage |
100V or 110V/120V/127V or 208V/220V/230V/240V |
 |
| AC Input Frequency |
50/60 Hz +/-0.5% |
 |
 |
AC OUTPUT
|
09
 |
| AC Output Waveform |
Sinewave |
 |
| AC Output Voltage |
100V or 110V/120V/127V or 208V/220V/230V/240V +/-2% |
 |
| AC Output Frequency |
50/60 Hz +/-0.5% |
 |
| AC Output Transfer |
0 ms |
 |
| AC Output Efficiency |
>95% |
 |
| AC Output Hamonic distortion |
<3% of T.H.D. at linear load |
 |
| AC Output Crest factor ratio |
3 : 1 |
 |
 |
PROTECTION
|
 |
| Protection Spike |
1015 Joules |
 |
| Protection Surge Protection |
120V (IEEE C62.41) / 230V (IEEE C61000-4-5 level 3) |
 |
| Protection Overload Protection |
125% for 1 minutes and 150% for 10 seconds |
 |
| Protection Short Circuit |
UPS output cut off immediately or input fuse/circuit breaker protection |
 |
 |
BATTERY
|
 |
| Battery Type |
sealed, maintenance-free lead acid batteries |
 |
| Battery Typical |
Recharge time to 90% full: 4 hours |
 |
| Battery Protection |
cut off without draining any current when battery is low |
 |
 |
BACKUP TIME
|
 |
| Battery Backup Time Full Load |
1u=4 min, 2u=7 min |
 |
| Battery Backup Time Half Load |
1u=10 min, 2u=15 min |
 |
 |
PHYSICAL
|
 |
| Physical Weight kgs RM |
1u=15.5, 2u=17.1 |
 |
| Physical Weight lbs RM |
1u=34.1, 2u=37.6 |
 |
| Physical Shipping Weight kgs |
1u=17.5, 2u=19.3 |
 |
| Physical Shipping Weight lbs |
1u=38.5, 2u=42.5 |
 |
| Physical Dimension mm RM |
1u=428x525x44, 2u=428x425x84 |
 |
| Physical Dimension inch RM |
1u=16.9x20.7x1.7, 2u=16.9x16.7x3.3 |
 |
| Physical Input Inlet |
NEMA 5-15 (120V) / IEC 320 (230V) |
 |
| Physical Receptacles |
NEMA 5-15 (120V) / IEC 320 (230V) |
 |
 |
INDICATOR
|
 |
| Indicator LCD |
Input/output voltage, frequency, on-line mode, back up mode, battery capacity, load level |
 |
 |
ALARM
|
 |
| Alarm Battery Backup |
Beep every 5 sec |
 |
| Alarm UPS Fault |
Continuous beeping sound and LCD display |
 |
 |
CONFORMANCE
|
 |
| Conformance Safety |
UL 1778, CE |
 |
 |
INTERFACE
|
 |
| Interface RS-232 |
Serial Port & USB |
 |
| Interface Option |
SNMP card |
 |
 |
ENVIRONMENT
|
 |
| Environment Temperature |
-20 ~ 50C / -4 ~ 122F |
 |
| Environment Humidity |
0 - 95%, non-condensing |
 |
| Environment Operation Temperature |
0 - 40C / 32 - 104F |
 |
| Environment Operation Elevation |
3500 meters max |
 |
| ShowOrder |
0 |
|
Click here to return
|
|
|
March 2011 |

GENERAL INFORMATION
|
 |
| Model Type |
VANGUARD LCD |
 |
| Model Name |
VGD-3000 |
 |
 |
AC INPUT
|
 |
| AC Input Capacity on Battery |
3000VA |
 |
| AC Input Voltage |
100V or 110V/120V/127V or 208V/220V/230V/240V |
 |
| AC Input Frequency |
50/60 Hz +/-0.5% |
 |
 |
AC OUTPUT
|
 |
| AC Output Waveform |
Sinewave |
 |
| AC Output Voltage |
100Vor 110V/120V/127V or 208V/220V/230V/240V +/-2% |
 |
| AC Output Frequency |
50/60 Hz +/-0.5% |
 |
| AC Output Transfer |
0 ms |
 |
| AC Output Efficiency |
>95% |
 |
| AC Output Hamonic distortion |
<3% of T.H.D. at linear load |
 |
| AC Output Crest factor ratio |
3 : 1 |
 |
 |
PROTECTION
|
 |
| Protection Spike |
1015 Joules |
 |
| Protection Surge Protection |
120V (IEEE C62.41) / 230V (IEEE C61000-4-5 level 3) |
 |
| Protection Overload Protection |
125% for 1 minutes and 150% for 10 seconds |
 |
| Protection Short Circuit |
UPS output cut off immediately or input fuse/circuit breaker protection |
 |
 |
BATTERY
|
 |
| Battery Type |
sealed, maintenance-free lead acid batteries |
 |
| Battery Typical |
Recharge time to 90% full: 4 hours |
 |
| Battery Protection |
cut off without draining any current when battery is low |
 |
 |
BACKUP TIME
|
 |
| Battery Backup Time Full Load |
6 min |
 |
| Battery Backup Time Half Load |
15 min |
 |
 |
PHYSICAL
|
 |
| Physical Weight kgs Tower |
33 |
 |
| Physical Weight lbs Tower |
72.6 |
 |
| Physical Shipping Weight kgs |
35.5 |
 |
| Physical Shipping Weight lbs |
78.1 |
 |
| Physical Dimension mm Tower |
225 x 425 x 360 |
 |
| Physical Dimension inch Tower |
8.9x16.7x14.2 |
 |
| Physical Input Inlet |
NEMA 5-15 (120V) / IEC 320 (230V) |
 |
| Physical Receptacles |
NEMA 5-15 (120V) / IEC 320 (230V) |
 |
 |
INDICATOR
|
 |
| Indicator LCD |
Input/output voltage, frequency, on-line mode, back up mode, battery capacity, load level |
 |
 |
ALARM
|
 |
| Alarm Battery Backup |
Beep every 5 sec |
 |
| Alarm UPS Fault |
Continuous beeping sound and LCD display |
 |
 |
CONFORMANCE
|
 |
| Conformance Safety |
UL 1778, CE |
 |
 |
INTERFACE
|
 |
| Interface RS-232 |
Serial Port & USB |
 |
| Interface Option |
SNMP card |
 |
 |
ENVIRONMENT
|
 |
| Environment Temperature |
-20 ~ 50C / -4 ~ 122F |
 |
| Environment Humidity |
0 - 95%, non-condensing |
 |
| Environment Operation Temperature |
0 - 40C / 32 - 104F |
 |
| Environment Operation Elevation |
3500 meters max |
 |
| ShowOrder |
0 |
|
Click here to return
|
|
|
March 2011 |

GENERAL INFORMATION
|
 |
| Model Type |
VANGUARD LCD |
 |
| Model Name |
VGD-2000 |
 |
 |
AC INPUT
|
 |
| AC Input Capacity on Battery |
2000VA |
 |
| AC Input Voltage |
100V or 110V/120V/127V or 208V/220V/230V/240V |
 |
| AC Input Frequency |
50/60 Hz +/-0.5% |
 |
 |
AC OUTPUT
|
 |
| AC Output Waveform |
Sinewave |
 |
| AC Output Voltage |
100V or 110V/120V/127V or 208V/220V/230V/240V +/-2% |
 |
| AC Output Frequency |
50/60 Hz +/-0.5% |
 |
| AC Output Transfer |
0 ms |
 |
| AC Output Efficiency |
>95% |
 |
| AC Output Hamonic distortion |
<3% of T.H.D. at linear load |
 |
| AC Output Crest factor ratio |
3 : 1 |
 |
 |
PROTECTION
|
 |
| Protection Spike |
1015 Joules |
 |
| Protection Surge Protection |
120V (IEEE C62.41) / 230V (IEEE C61000-4-5 level 3) |
 |
| Protection Overload Protection |
125% for 1 minutes and 150% for 10 seconds |
 |
| Protection Short Circuit |
UPS output cut off immediately or input fuse/circuit breaker protection |
 |
 |
BATTERY
|
 |
| Battery Type |
sealed, maintenance-free lead acid batteries |
 |
| Battery Typical |
Recharge time to 90% full: 4 hours |
 |
| Battery Protection |
cut off without draining any current when battery is low |
 |
 |
BACKUP TIME
|
 |
| Battery Backup Time Full Load |
7 min |
 |
| Battery Backup Time Half Load |
15 min |
 |
 |
PHYSICAL
|
 |
| Physical Weight kgs Tower |
31.1 |
 |
| Physical Weight lbs Tower |
68.4 |
 |
| Physical Shipping Weight kgs |
33.6 |
 |
| Physical Shipping Weight lbs |
73.9 |
 |
| Physical Dimension mm Tower |
225 x 425 x 360 |
 |
| Physical Dimension inch Tower |
8.9x16.7x14.2 |
 |
| Physical Input Inlet |
NEMA 5-15 (120V) / IEC 320 (230V) |
 |
| Physical Receptacles |
NEMA 5-15 (120V) / IEC 320 (230V) |
 |
 |
INDICATOR
|
 |
| Indicator LCD |
Input/output voltage, frequency, on-line mode, back up mode, battery capacity, load level |
 |
 |
ALARM
|
 |
| Alarm Battery Backup |
Beep every 5 sec |
 |
| Alarm UPS Fault |
Continuous beeping sound and LCD display |
 |
 |
CONFORMANCE
|
 |
| Conformance Safety |
UL 1778, CE |
 |
 |
INTERFACE
|
 |
| Interface RS-232 |
Serial Port & USB |
 |
| Interface Option |
SNMP card |
 |
 |
ENVIRONMENT
|
 |
| Environment Temperature |
-20 ~ 50C / -4 ~ 122F |
 |
| Environment Humidity |
0 - 95%, non-condensing |
 |
| Environment Operation Temperature |
0 - 40C / 32 - 104F |
 |
| Environment Operation Elevation |
3500 meters max |
 |
| ShowOrder |
0 |
|
Click here to return
|
|
|
March 2011 |

GENERAL INFORMATION
|
 |
| Model Type |
VANGUARD LCD |
 |
| Model Name |
VGD-1000 |
 |
 |
AC INPUT
|
 |
| AC Input Capacity on Battery |
1000VA |
 |
| AC Input Voltage |
100V or 110V/120V/127V or 208V/220V/230V/240V |
 |
| AC Input Frequency |
50/60 Hz +/-0.5% |
 |
 |
AC OUTPUT
|
 |
| AC Output Waveform |
Sineware |
 |
| AC Output Voltage |
100V or 110V/120V/127V or 208V/220V/230V/240V +/-2% |
 |
| AC Output Frequency |
50/60 Hz +/-0.5% |
 |
| AC Output Transfer |
0 ms |
 |
| AC Output Efficiency |
>95% |
 |
| AC Output Hamonic distortion |
<3% of T.H.D. at linear load |
 |
| AC Output Crest factor ratio |
3 : 1 |
 |
 |
PROTECTION
|
 |
| Protection Spike |
1015 Joules |
 |
| Protection Surge Protection |
120V (IEEE C62.41) / 230V (IEEE C61000-4-5 level 3) |
 |
| Protection Overload Protection |
125% for 1 minutes and 150% for 10 seconds |
 |
| Protection Short Circuit |
UPS output cut off immediately or input fuse/circuit breaker protection |
 |
 |
BATTERY
|
 |
| Battery Type |
sealed, maintenance-free lead acid batteries |
 |
| Battery Typical |
Recharge time to 90% full: 4 hours |
 |
| Battery Protection |
cut off without draining any current when battery is low |
 |
 |
BACKUP TIME
|
 |
| Battery Backup Time Full Load |
7 min |
 |
| Battery Backup Time Half Load |
15 min |
 |
 |
PHYSICAL
|
 |
| Physical Weight kgs Tower |
16.2 |
 |
| Physical Weight lbs Tower |
35.6 |
 |
| Physical Shipping Weight kgs |
18.2 |
 |
| Physical Shipping Weight lbs |
40.0 |
 |
| Physical Dimension mm Tower |
152x420x238 |
 |
| Physical Dimension inch Tower |
6.0x16.5x9.4 |
 |
| Physical Input Inlet |
NEMA 5-15 (120V) / IEC 320 (230V) |
 |
| Physical Receptacles |
NEMA 5-15 (120V) / IEC 320 (230V) |
 |
 |
INDICATOR
|
 |
| Indicator LCD |
Input/output voltage, frequency, on-line mode, back up mode, battery capacity, load level |
 |
 |
ALARM
|
 |
| Alarm Battery Backup |
Beep every 5 sec |
 |
| Alarm UPS Fault |
Continuous beeping sound and LCD display |
 |
 |
CONFORMANCE
|
 |
| Conformance Safety |
UL 1778, CE |
 |
 |
INTERFACE
|
 |
| Interface RS-232 |
Serial Port & USB |
 |
| Interface Option |
SNMP card |
 |
 |
ENVIRONMENT
|
 |
| Environment Temperature |
-20 ~ 50C / -4 ~ 122F |
 |
| Environment Humidity |
0 - 95%, non-condensing |
 |
| Environment Operation Temperature |
0 - 40C / 32 - 104F |
 |
| Environment Operation Elevation |
3500 meters max |
 |
| ShowOrder |
0 |
|
Click here to return
|
|
|
March 2011 |

Features
- Extend backup time by adding ext. battery packs.
- Boost/buck, on-line, battery status LED display.
- Line interactive design.
- Boost and buck AVR.
- Hot swappable battery by users.
- Fully digitized microprocessor controlled.
- Smart RS-232 communication port.
- Lightning and surge protection.
- Short circuit and overload protection.
- 50/60Hz frequency auto sensing.
- Tel/modem internet spike protection.
- Site wiring fault warning (110V only).
- Smart power management with software.
- Cold start (DC power on).
- Advanced battery management (ABM).
- Energy saving (UPS sleep mode).
Specifications
Model: KXL-1000AP, KXL-2000AP.
Capacity: 1000VA/600W, 2000VA/1200W.
Voltage: +/-25% at line input.
Frequency: 50 or 60Hz +/-10% (auto sensing).
Voltage (on battery): simulated sine wave at +/-5% of nominal.
Frequency (on battery): 50 or 60Hz +/-0.5%.
Voltage Regulation (AVR): AVR automatically increase output voltage
15% above input voltage if -9% to -25% of nominal. AVR decrease output
voltage 13% below input voltage if +9% to +25% of nominal.
Transfer: 2/4 milliseconds, including detection time.
Protection & filtering:
Spike protection: 320 joules, 2ms.
EMI/RFI filter: 10dB at 0.15MHz, 50 dB at 30MHz.
Overload protection: UPS automatic shutdown if overload exceeds 110% of nominal at 60 seconds and 130% at 3 seconds.
Unit input: circuit breaker for overload & Short circuit protection.
10Base-T port: network (UTP, RJ-45) compatible jacks.
Short circuit: UPS output cut off immediately or input fuse protection.
Net Weight kg (lbs): 19.8 (43.56 lb), 28.9 (63.58 lb).
Shipping Weight Kg (Ibs): 21 (46.2 lb), 31.4 (69.08 lb).
Dimension WxDxH (mm): 130 x 382 x 201 (5.1" x 15" x 7.9"), 169 x 438.5 x 215 (6.7" x 17.3" x 8.5").
Input inlet: IEC 320 power inlet.
Receptacles: NEMA 5-15R(115V) / IEC320 female appliance coupler(230V).
Dry contact: AC fail, battery low, shutdown signal.
RS-232 interface: bi-directional communication port.