![]() Features
Model: KXL-1000AP, KXL-2000AP. Capacity: 1000VA/600W, 2000VA/1200W. Voltage: +/-25% at line input. Frequency: 50 or 60Hz +/-10% (auto sensing). Voltage (on battery): simulated sine wave at +/-5% of nominal. Frequency (on battery): 50 or 60Hz +/-0.5%. Voltage Regulation (AVR): AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal. Transfer: 2/4 milliseconds, including detection time. Protection & filtering: Spike protection: 320 joules, 2ms. EMI/RFI filter: 10dB at 0.15MHz, 50 dB at 30MHz. Overload protection: UPS automatic shutdown if overload exceeds 110% of nominal at 60 seconds and 130% at 3 seconds. Unit input: circuit breaker for overload & Short circuit protection. 10Base-T port: network (UTP, RJ-45) compatible jacks. Short circuit: UPS output cut off immediately or input fuse protection. Net Weight kg (lbs): 19.8 (43.56 lb), 28.9 (63.58 lb). Shipping Weight Kg (Ibs): 21 (46.2 lb), 31.4 (69.08 lb). Dimension WxDxH (mm): 130 x 382 x 201 (5.1" x 15" x 7.9"), 169 x 438.5 x 215 (6.7" x 17.3" x 8.5"). Input inlet: IEC 320 power inlet. Receptacles: NEMA 5-15R(115V) / IEC320 female appliance coupler(230V). Dry contact: AC fail, battery low, shutdown signal. RS-232 interface: bi-directional communication port. Click here to return |